Corrosion protection armoured computer cable
Product introduction:
The product is low capacitance, low inductance, distributed type instrument signal cable of perfect shield and anti-interference performance, it can reliably transmit feeble analog signal and digital signal, and its explosion-proof safety is prominently better than general DCS cable and control cable. The product is widely used to transmit auto-control signals in the places where exist explosion danger such as chemical, power, coal gas engineering and mine, etc, or other places where require higher explosion-proof safety.
Executive Standard
Q/AHXYLY02-2009 equivalent to British standard BS5308
Operational Performances
1. Rated AC voltage: U0/U 300/500V
2. Max. working temperature of conductor core: 70°C, 105°Cand 135°C
3. Lowest ambient temperature: for fixed laying:-40°C,non-fixed laying:-20°C
4. Allowed minimum bending radius of cable: for non-armored cable, not less than 6 times of cable outer diameter; for copper tape shield or annoyed cable, not less than 12 times of cable outer diameter.
Main Technical Data
Item | Unit | Data |
Working capacitance | PF/m | ≤80 |
Capacitance unbalance | PF/m | ≤1 |
Distributed inductance | µH/m | ≤0.6 |
Inductance/resistance | µH/Ω | ≤25 |
Induction voltage (interference magnetic field 400A/m) | mV | ≤5 |
Static induction voltage (static voltage 20kV) | V | ≤1 |
Radiation field penetration (interference field 200MHz, 120dB) | dB | ≤66 |
Insulation resistance at 20°C | MΩ.km | ≥5000 |
Test voltage | V/1min | 2000 |
Flame-retardant character (test to be performed in terms of GB/T12666.5-1990) |
| Type A |
Basic Types and Descriptions
Type | Designation |
IAJYPVP | Copper-core PE insulated, PVC sheathed, woven copper wire separate shield, general shield,intrinsically safe DCS cable |
IAJYPVRP | Copper-core PE insulated, PVC sheathed, woven copper wire separate shield, general shield,intrinsically safe DCS flexible cable |
IAJYP1VP1 | Copper-core PE insulated, PVC sheathed, tinning woven copper wire separate shield, general shield, intrinsically safe DCS cable |
IAJYP1VRP1 | Copper-core PE insulated, PVC sheathed, tinning woven copper wire separate shield, general shield,intrinsically safe DCS flexible cable |
IAJYP2VP2 | Copper-core PE insulated, PVC sheathed, copper tape separate shield and general shield, intrinsically safe DCS cable |
IAJYP3VRP3 | Copper-core PE insulated, PVC sheathed, aluminum/plastic compound tape separate shield and general shield, intrinsically safe DCS flexible cable |
IAJYP1VRP3 | Copper-core PE insulated, PVC sheathed, tinning woven copper wire separate shield and aluminum/plastic compound tape general shield, intrinsically safe DCS flexible cable |
IAJYP1V22RP3 | Copper-core PE insulated, PVC sheathed, tinning woven copper wire separate shield and aluminum/plastic compound tape general shield, steel tape armored intrinsically safe DCS flexible cable |
IAJYP1V32PR | Copper-core PE insulated, PVC sheathed, tinning woven copper wire separate shield and woven copper wire general shield, small-gauge steel wire armored intrinsically safe DCS flexible cable |
ZR-IAJYPVP | Copper-core PE insulated, 105°Cflame-retardant sheathed, woven copper wire separate shield and general shield, intrinsically safe DCS cable |
ZR135-IAJYPVRP | Copper-core PE insulated, 135°Cflame-retardant sheathed, woven copper wire separate shield and general shield, intrinsically safe DCS flexible cable |
ZR-IAJYP1VP1 | Copper-core PE insulated, 105°Cflame-retardant sheathed, tinning woven copper wire separate shield and general shield, intrinsically safe DCS cable |
ZR135-IAJYP1VRP1 | Copper-core PE insulated, 135°Cflame-retardant sheathed, tinning woven copper wire separate shield and general shield, intrinsically safe DCS flexible cable |
ZR-IAJYP2VRP2 | Copper-core PE insulated, 105°Cflame-retardant sheathed,copper tape separate shield and general shield, intrinsically safe DCS flexible cable |
ZR135- IAJYPVRP3 | Copper-core PE insulated, 135°Cflame-retardant sheathed, woven copper wire separate shield, aluminum/plastic compound general shield, intrinsically safe DCS flexible cable |
ZR-IAJYPV22RP1 | Copper-core PE insulated, 105°Cflame-retardant sheathed, woven copper wire separate shield, tinning copper wire general shield, steel tape armored intrinsically safe DCS flexible cable |
ZR135- IAJYP1V32RP | Copper-core PE insulated, 135°Cflame-retardant sheathed, tinning copper wire separate shield, woven copper wire general shield, small-gauge steel tape annoyed intrinsically safe DCS flexible cable |
1.Code and definition
Item | Code | Definition |
Flame-retardant character | / ZR ZR-135 | Non flame-retardant that can be omitted General flame-retardant 135°C flame-retardant |
Series code | IAJ | Intrinsically safe explosion-proof DCS cable |
Insulation material | Y V VD E | PE PVC Low smoke and low halogen PVC Low smoke and halogen-free polyolefin |
Shield material | P P1 P2 P3 | Woven copper wire shield Tinning copper wire Copper tape Aluminum/plastic compound tape |
Armor material | 22 32 | Steel tape armor Small-gauge steel wire armor |
Heat-resistant grade | 70 105 135 | Max.working temperature is 70°C,can be omitted Max.working temperature is 105°C Max.working temperature is 135°C |
Conductor type | A B R | Single-strand conductor 7-strand twisted conductor (type A&B are marked after specification) Multiple-strand flexible conductor |
Specification |
| Pairs (or groups) x cores of each pair(or group) x conductor core section mm2 Pairs (or groups): 1,2,3. .. .24 Core of each pair (or group): 2, 3 Conductor core section s: 0.5, 0.75, 1.0, 1.25, 1.5, 2.5 (mm2) |
Note: Intrinsically safe cable required to be high-temperature-resistant, oil-resistant and acid/alkali corrosion-resistant, its types and materials can be referred to relevant items of computer cable. Based on the above-described type description for intrinsically safe explosion-proof DCS cable, different combinations can be selected to meet requirements.
SpecificationSize
1.IAJYPVP, IAJYP3VP3,IAJYP2VP2, ZR-IAJYPVP, ZR-IAJYP3VP3, ZR-IAJYP2VP2(Twin type)
Cont table
Note: The outer diameter of armored cable could add 4.0mm
2.IAJYPVP, IAJYP3VP3,IAJYP2VP2, ZR-IAJYPVP, ZR-IAJYP3VP3,ZR-IAJYP2VP2(Triplet)
Cont table
Note: The outer diameter of armored cable could add 4.0mm
Marking Examples:
Example 1: Intrinsically safe DCS flexible cable selectingcopper-core PE insulation, PVC sheath, woven copper wirepair shield and general shield, nominal section of conductorcore is 1.0mm2, 19-strand twisted conductor with three 3-wire groups, can be expressed by:IAJYPVRP 3 x 3 x 1.0
Example 2: Intrinsically safe DCS cable selecting copper-core PE insulation. 105°Cflame-retardant PVC sheath.aluminum/plastic compound pair shield, woven copper wire general shield, nominal section of conductor core is 1.5mm2, 2pairs: Conductor-core applies single-strand copper wire: ZR-IAJYP3VP-105 2 x 2 x 1.5(A)
Conductor-core applies 7-strand twisted wire:
ZR-IAJYP3VP-105 2 x 2 x 1.5(B)
Packaging Detail: | international wooden drums or according to your requirement. |
Delivery Detail: | In 15days or as the quantity you required |
1.Free samples can be afford if needed.
2.2 years warranty after selling
Company Information
- Q: Hi,I have a set of Sony speakers that are a few years old. They have no power cable (nowhere to plug a cable in either) and the aux cable has no jacks. It is just two split wires. How can I connect them to my TV?Thanks,Aaron
- Your unpowered (standard) speakers do not Plug in to a TV. They Plug in to an amplifier/receiver like all other standard speakers in this world do. Your speaker wires are not AUX cables, they are eh, speaker wires. speakers left over from all in one movie disc player/radios wont match up with normal recievers. You throw them away with the defunct disk player (HTiB). I do not believe for a second you do not know what a speaker is, or how normal speakers connect. This technology has been around for a century.
- Q: got 1 amp in the back,i want to add another amp at the front without a distrubuter,could i trail another power cable from the battery to the amp?
- you will could run a twine to each and each amp using a fused distrobution block as pronounced. A 60 amp fuse won't be that massive for automobile audio. some amps can pull eighty amperes. This fuse is quite in basic terms there to guard the potential twine from being shorted.
- Q: YJV three-core cable and the difference between the four-core cable
- Change the data line ah, often with non-original battery will be filled with bad
- Q: I lost my PS3 power cable but I got one from an old pc and it does work but am i better off using my old cable?Does it affect my PS3's performance?
- some PS3s have usual means furnish. to comprehend which one you have you are able to desire to open it. in case you do no longer prefer to open it (and void the guaranty) - use means converter. notice: for PS3 you will prefer a minimum of four hundred Watt. As for means cable itself - relies upon on the socket on your means converter.
- Q: Have a 480 volts 3 phase 16 amp motor. Need 400 ft of extention cord. Is is OK to use a SOOW 10/4 cable, the voltage drop is 2.67%(12 volts). Machine is powerd by a generator that I can run at 500 volts to counter the voltage drop.8/4 cable cost twice as much, but the voltage drop is 1.7%(8 volts).
- If you have the ability to increase the voltage to compensate for the volt drop and the cable has sufficient current carrying capacity, then you are fine. The volt drop will cause a little wasted power but nothing compared to cable costs probably. Presumably your boosted voltage generator wont be powering anything else or that will give you problems Edit, Cables are rated in rms voltage
- Q: I just got done building my new computer, and am putting in my cd-room's.When i plug in the power to them they will open, but when i connect them to the motherboard with the ide cable they wont open.And yes i have everything plugged in right.
- did you try a different CD rom? might just be broken.
- Q: Two weeks ago, my 1 yr 19 lcd monitor began to flicker? Why? The power cord and usb cable are secure?
- I've had a similar thing happen with my 17 GEM monitor. Eventually, I relocated the monitor and redid all the wiring and the flickering ultimately stopped. I'd wager it's a wire issue.
- Q: I have a HP Printer and have lost my power cable, now I am having trouble identifying the type of lead that goes in the hole (see pic link)I am in the UK
- What is the model number of your HP printer? Is it the C3180? I am looking for a power adapter for the C3180, and I believe the HP AC Adapter model number 0957-2178 is the correct one, but I'll find out for sure in a few days as I am ordering one. If you tell me the model number of your HP printer, I may be able to help you out because I have learned a lot about HP printer AC Adapters in the last few hours.
- Q: HelloWhen i turn on my computer without 4 pin ATX +12 volt power cable my computer starts and everything goes fine but when i connect it to my motherboard my computer does not start.i want to know that is this cables necessary for normal computer operation or i can go without it??I am using ATX 20+4 pin main power cable for my motherboard power.
- As far as i know you need both connected. you might have updated your bios that's why your four pin isn't working. Do check the power configurations in your bios. I am definitely sure that's where the problem is. Hope that helps.
- Q: What is the difference between rubber insulation and paper insulated power cables?
- When the cable is laid on the multi-layer bracket, the cables are arranged from top to bottom, the first layer is the high voltage cable, followed by the low voltage power cable. The control cable is placed on the lower part of the power cable. At the bottom of the instrument cable, when the low voltage power cable With the instrument cable in the same layer of laying, should be added partition isolation. Computer communication coaxial cable, full length are required to shield the use of closed trunking.