Teflon Insulated Wire
- Loading Port:
- China Main Port
- Payment Terms:
- TT or LC
- Min Order Qty:
- 1000 Meters m
- Supply Capability:
- 80000 Meters per Week m/month
OKorder Service Pledge
OKorder Financial Service
You Might Also Like
*Nominal Voltage: 300V
*Temperature Range: -100º C ~ +150º C
*O. D. Tolerance: ± 0.15mm
*Testing Voltage: 2000V
*Conductor: Tinned & Silver & Nickel Copper
*Insulator: FEP TEFLON
*Colours: White-Blue-Red-Black-Brown-Yellow-Green-Transparent-Yellow/Green
Conductor | Insulator | Electrical Characteristic | ||||
Conductor construction NO.Xφmm | Diameter mm | Insulator Thick mm | Over Diameter mm | Realst.max Cuc,c 20°C ohm/km | Permissble ampacity 20°C-AMR | |
30 | 1*0.25 | 0.25 | 0.2 | 0.65 | 347 | 0.66 |
28 | 1*0.31 | 0.31 | 0.2 | 0.71 | 218 | 1.05 |
26 | 7*0.15 | 0.46 | 0.33 | 1.12 | 145.65 | 1.61 |
19*0.10 | 0.5 | 0.33 | 1.16 | 145.65 | 1.61 | |
24 | 7*0.20 | 0.61 | 0.33 | 1.27 | 85.9 | 2.57 |
19*0.12 | 0.6 | 0.33 | 1.26 | 85.9 | 2.57 | |
22 | 7*0.25 | 0.76 | 0.33 | 1.42 | 54.3 | 4.36 |
19*0.15 | 0.76 | 0.33 | 1.42 | 54.3 | 4.36 | |
20 | 7*0.31 | 0.95 | 0.33 | 1.61 | 34.6 | 6.94 |
19*0.19 | 0.96 | 0.33 | 1.62 | 34.6 | 6.94 | |
18 | 7*0.39 | 1.19 | 0.33 | 1.85 | 21.8 | 11.01 |
19*0.235 | 1.18 | 0.33 | 1.84 | 21.8 | 11.01 | |
16 | 7*0.50 | 1.53 | 0.33 | 2.19 | 13.5 | 17.52 |
19*0.30 | 1.51 | 0.33 | 2.17 | 13.5 | 17.52 |
- Q:I have an old house (built in 1962) and after testing all of my outlets, have confirmed that none of them are grounded. The house is made of brick, so it would be extremely expensive to run new circuits through the house. I really only need 1 or 2 outlets to be grounded so that I can protect my expensive equipment from damage. So what I wanted to know is if I could buy a spool of 10 gauge solid copper core insulated grounding wire, drill a hole through the brick behind the outlet, connect to the outlet and run the other end of the wire around the outside of the house to the main box. Would that be safe? Would it hold up to power spikes?
- 1962 is not that old. You will likely have circuit breakers rather than fuses. Your service entrance must be grounded (or the utility would not have provided service). (1) Your branch circuits should be supplied by BX (armored cable, either AWG#14 or AWG#12) the cable armor is the ground path back to the fuse or breaker panel. If your house is wired with ROMEX (amateur work) the ROMEX (plastic covered cable) it should have three conductors: black, white, and green. Green is the ground conductor. (2) Many Service Entrances (fuse, or circuit breaker distribution panels) are grounded to water mains. However, many water meters are installed with Dresser Couplings (Rubber insulated compression fittings) which are non-conductive. The ground connection must be made on the street side of the water meter (if you use a public water supply). It's more likely that you have a poor ground path than no ground path. Ground rods driven into the earth are helpful but generally poor.
- Q:I have a pet rat with quite a persistant chewing problem. He constantly chews through wires when I let him free roam and he is not the first rat I have ever had that has done this, but he is to the extent that he chews the wires. He chews them right down so that the metal inside is hanging out. Today I picked up one of the wires without realising what he had done and got quite a nasty electric shock on my hand which actually broke the skin very slightly! Needless to say today is the very last time he free roams unsupervised and I realise I have been foolish to let him do so for so long. But I am just wondering, if I can get a shock like that, howcome when he is chewing the wire he (and the other rats I've had do the same thing) is always completely unharmed.let alone how do they not die? - If a human being can get a rather forceful and painful shock, how can the force not kill something as small as a rat?!
- Are you searching for a short-term restore or an eternal one? Rats can bite with the aid of cinder blocks in the event that they wish. One one our nearby puppy shops has a twine type in-closure for them to play in (feels like a twine play pen notwithstanding that's small and the facets fold in for storage, perchance you are going to be able to take off one edge and connect it to the edge of your cage. We paid about $15.00 for ours. notwithstanding, i would make positive you keep plenty of issues for them to bite on interior the cage in hopes that they wont bite the walls.
- Q:can i just connect a regular electrical wire on there ?
- Buy a new plug. Wire it to the cord with the correct polarity. Spicing a cord is a violation of the electric code. I don't care what kind of tape the make believe electrician tells you to use.
- Q:I have a lot of equipment in my local and I'm suffering about big cargo in electric wire for your knowledge voltage 220 Ventensity 30 Awire Demetre 2.5 mmwhat should I do for avoid the damaging of disgenctor or burning of wire
- The wires too small for 30A! You need to upgrade the wire size or lower the amperage! The set-up you now have is just begging for a fire! Be Careful! ;-)
- Q:Hi, I have a 60 year old house. While doing an addition, I discovered that the outlets were running from the panel, through the kitchen, to the living room, and then the garage. Was this the normal way to wire back then?? Every time I have the TV( living room), washer (garage), Frig and microwave (kitchen) on, the circuit breaker trips. I am doing the wiring for my new addition, and can put the living room and garage on a seperate circuit. Is this wise?? It sounds like a good idea, but I want to make sure.Thanks for your timepb4sc
- Rewiring sounds like a good idea. You need at least 2 seperate 20 amp circuits for your kitchen. Depending on your electrical needs in the garage I would probably install at least 2 (dedicate 1 for the washer) also. 1 in the living room is fine.
- Q:What is the role of the wire of the two-color line `` `` ``
- And now quickly put the PVC pipe into the also too late! It's dangerous to use it later! Suggestions to improve now! Or remove the sub-board from the new board! Will not damage the material! Please be careful!
- Q:What is the role of the two-color wire and monochrome wire?
- 1. Birds are just standing on a wire can not form a loop so there is no electric shock. 2. Birds feet from the distance even in the high voltage line will not form a step voltage.
- Q:Can I run a ground wire from and electrical motor to a bolt that is screwed into wood? Will this work? I have a hot tub and replaced the motor, the new motor has the thick copper ground wire mounted on the back so the wire I have is too short now to reach to where it was grounded before. I ran the wire from the motor to a bolt that is screwed into the wood frame of the hot tub. The old ground went from the motor to the metal brain box witch is also attached to wood so I figured my alternative fix is OK?
- You should run were that is terminated at the green grounding lug in the service panel. Also connect it to 2 driven ground rods at least 6 feet apart. You can get these rods at almost any electrical supply house
- Q:i have only three buttons, 2 light bulbs, and tons of wiresi need to make button #1 light up light #1and button #2 light up light #2and button #3 light up light #1 and 2thanks5 stars for correct working answer
- A C or D C?
- Q:I'm creating a parallel circuit with 4 branches/conductors, which are connected to an AC power source emitting a signal of 5V p-p at 60 kHZ in sine waveform.Can I use any old copper wires? Or should I use a specific type/heavier type of wiring for this? Any good ones you can suggest?Thanks!
- An copper wire would be fine, unless you are drawing a lot of current. From what I recall of your previous questions, the current is in the mA range, so you could use any wire from #32 on up. And I repeat my previous statement, you are playing with passing electrical currents through the human body. This question reinforces my previous opinion about your lack of any knowledge about electricity. Please, before you kill someone, find a different toy. .
1. Manufacturer Overview |
|
---|---|
Location | Henan,China |
Year Established | 1997 |
Annual Output Value | |
Main Markets | North America South America Eastern Europe Southeast Asia Africa Oceania Mid East Eastern Asia Western Europe |
Company Certifications | CCC;ISO9001-2008;SGS |
2. Manufacturer Certificates |
|
---|---|
a) Certification Name | |
Range | |
Reference | |
Validity Period |
3. Manufacturer Capability |
|
---|---|
a)Trade Capacity | |
Nearest Port | |
Export Percentage | 81% - 90% |
No.of Employees in Trade Department | |
Language Spoken: | |
b)Factory Information | |
Factory Size: | 50,000-100,000 square meters |
No. of Production Lines | Above 10 |
Contract Manufacturing | OEM Service Offered |
Product Price Range |
Send your message to us
Teflon Insulated Wire
- Loading Port:
- China Main Port
- Payment Terms:
- TT or LC
- Min Order Qty:
- 1000 Meters m
- Supply Capability:
- 80000 Meters per Week m/month
OKorder Service Pledge
OKorder Financial Service
Similar products
Hot products
Hot Searches
Related keywords