PVC Insulated and Sheathed Flat Cable 450/750V
- Loading Port:
- Shekou
- Payment Terms:
- TT or LC
- Min Order Qty:
- 100 roll
- Supply Capability:
- 20000 roll/month
OKorder Service Pledge
OKorder Financial Service
You Might Also Like
1.Short Description:
High quality 2Cores & 3 core bvvb cable flat cable PVC Insulated and sheathed 300/500V
These cables are used for general purpose, as building wire for power, lighting and control wire to electrical appliances, suitable for use in conduit and for fixed, protected installation
1. Voltage rating: 300/500V or 450/750V
2. Standard applied: IEC60227, BS6004, GB/T5023, JB/T8734
3. Conductor: bare solid/stranded copper; class 1 for 1.0mm2, 1.5mm2 and 2.5mm2; class 2 for the others
4. Insulation and sheath: PVC
5. Max. working temp.: 70°C, can be90°C and 110°C as per requirement
6. Main colors:sheath--white/black/grey; 2cores--red&black; 3cores--red, yellow&blue
7. Minimum bending radius: Up to 10mm², 3 x overall diameter;10mm² to 25mm², 4 x overall diameter
8. The cable can be of flame retardance, fire resistance and other property
9. Remark: We are able to produce 2C, 2C+E, 3C & 3C+E by AS/NZS
2.Parameter
3.Pictures
4.Main manufacturing procedure
1. Copper wire drawing and annealing
2. Copper wire stranding
3. Outer sheath extruding and labeling
4. Spooling
- Q:What is the depth of the 10KV high-voltage pole?
- According to the current standard of China's wire and cable models - . BVVR is the wire model, said the recording of ethylene insulation, recorded vinyl jacket soft core copper sheath line, is the market to see a long two or three Wrapped together in the wire, if BVV is hard core, if BLVV is aluminum core ****. . KVVR is the cable model, and is the control cable model. R represents the soft core, and no L represents the copper core.
- Q:How to calculate the wattage wattage and power of the wire?
- . chipset . the quality of the capacitor, the number of . other accessories configuration
- Q:Four air-conditioning, two electric water heaters at the same time need to use the number of square wires more
- 27KW * 1.5A / KW = 40.5A (per phase current) 36KW * 1.5A / KW = 54A (each phase current) 10 square line maximum withstand current 40A, switch to 3 * 16 +2 * 10 cable, With M1-63A / . contactor replaced by CJX2-. with two 10 square lines and parallel line, 25-ping line of safe current in the 80 or so, with two small, water heater lead or replaced It, if only temporary can also be used for a long time or for a washing machine and the energy of the energy-saving lamps add up to 200 watts, can be ignored.
- Q:i have a wired xbox 360 controller and it had a shortage in it . so i fix the shortage now the controller wont come on.i got me a new usb breakaway cord and it still wont work.how do i fix it without buying a new one
- well depends on how you shorted it out now this works for a lot of corded things like keyboard wires electrical wires your gonna want to go to the inside of the wire where there shood be three wires positive negative and copper if any of these are damaged in the slightest your gonna want cut the wire in half and take their inner wires and twist both ends of the cut wire and twist them together and wrap electrical tape around them do this for each wire now only do this if an other process dosnt work or your desperate granted it does work i personally have done this with electrical cords mouse wires printer wires this process will get the electrical current flowing again so this may work with you corded controller again depends on what you did to short it out now here's the simple answer it may jus be old all controllers have an expiration date in some way hoped i helped
- Q:I am putting all my lighting on a single circuit, and have a question. The main feed from the panel to the lights first goes to a double gang switch, one switch controls the lights on half of the main room in the basement, the other controls the lights in the other half of the main room in the basement. Then I need the main feed to continue to three other switches in three other rooms in the basement. Do I just wire nut the black wired and wire nut the white wires, and continue running to the next switch. So if that is the case, then am I correct in saying that in the double gang switch I will have one wire nut with the ground wires, one wire nut with 4 black wires, and one wire nut with 4 white wires? Please help with this matter, I want to do this correct, so my house doesn't burn down.By the way I am using 14/2 wire.
- You are correct in the way you described your circuit and what you want to do. Like the other person mentioned, make sure you tap off the black wire before the existing switches and not after. You are correct, all the blacks in a wire nut, all the whites in another, and all the grounds in another. The other thing to consider is overloading the circuit. Figure on using 12 amps maximum out of your 15 amp circuit. That is a total of 1440 watts worth of lights. About 14, 100 watt incandescent bulbs. As long as your #14 wire is protected with a 15 amp circuit breaker, your connections are tight, and all the connections are in boxes, you won't burn the house down. Email if you need more advice.
- Q:There is a blue, gray, one side is the yellow side is green three lines, how to distinguish between the line of fire, zero line, ground? More
- If only two lines and is a single-phase power is so red and green if the three-phase four-line yellow-green red fire. Blue or black or two-color line connected to a simple point from the color to distinguish between bright and bright for the fire line bleak for the zero line
- Q:Cant find a haynes manual and the facvtory manuals are too expensive. I'm looking for a downloadable electrical diagram for a 1984 300sd (126)
- Legends and artifacts relationship back 1000's of years have ignited guy's mind's eye for some years to centuries with theories of historical astronauts and alien beings from different planets. Sightings of UFOs or unidentified flying gadgets of various sizes, shapes and different features have been recorded world extensive for hundreds of years, probable 1000's. In widespread television exhibits, that's alleged that sky people are purportedly recorded as having delivered stepped forward way of existence to the hominids who've lived on earth. in accordance to those legends, supposedly, this first touch had got here approximately formerly, following cataclysm. some memories relate this civilizing experience to have happened countless situations for the time of Earth's background. Geological, paleontological, anthropological and archaeological information show that there have certainly been many cataclysms in this earth, countless on a worldwide point, with climate exchange and mass extinction. The memories allegedly recount that once the form of disaster, many surviving people have been decreased to the Stone Age yet that extra stepped forward humanoids descended from spacecraft and reestablished civilization. Are those claims authentic? have been those sky people extraterrestrial beings? Have there been extraterrestrial beings between us all alongside? Or is all of it only an phantasm?
- Q:I have 60 ft and 40 ft of the 1/0 electrical THHN STRANDED wire. I don;t know if be possible to join both, due to I need 95 ft. Does anybody give me an idea? Thanks.
- If you intend to pull this wire into a pipe, NO. It is a Code Violation to have a spice in an enclosed raceway. If you can set an accessible box at the spilce point, YES. If it will be in a gutter or cable tray, then yes. These days a common way is to use a Polaris Tap. Quick, easy and cost effective. If you are not using this for electrical purposes, a split-bolt (no tape required) is quick and cheap.
- Q:Electrical wiring for a school building or swimming pool
- Engineer is not allowed to do this type of work for school because he is not qualified as an electrician. About $60 per hour charge by electrician.
- Q:What is the maximum load of 2.5 square millimeters of wire?
- 2.5 square millimeters of copper power line safety carrying capacity 28A. The following is the formula other you can calculate P = 1.732UIX0.8
1. Manufacturer Overview |
|
---|---|
Location | |
Year Established | |
Annual Output Value | |
Main Markets | |
Company Certifications |
2. Manufacturer Certificates |
|
---|---|
a) Certification Name | |
Range | |
Reference | |
Validity Period |
3. Manufacturer Capability |
|
---|---|
a)Trade Capacity | |
Nearest Port | |
Export Percentage | |
No.of Employees in Trade Department | |
Language Spoken: | |
b)Factory Information | |
Factory Size: | |
No. of Production Lines | |
Contract Manufacturing | |
Product Price Range |
Send your message to us
PVC Insulated and Sheathed Flat Cable 450/750V
- Loading Port:
- Shekou
- Payment Terms:
- TT or LC
- Min Order Qty:
- 100 roll
- Supply Capability:
- 20000 roll/month
OKorder Service Pledge
OKorder Financial Service
Similar products
Hot products
Hot Searches