Technical specifications

Table 2.3: Technical Parameters of QD200 Series Frequency Inverters

ITEM

SPECIFICATIONS

Main

Input

Rated voltage and frequency

Single-phase 200V class:  200V-240V,50Hz/60Hz

3-phase 400V class:  380V-480V , 50Hz/60Hz

Allowable value of change

Voltage: 380V-15% ~ 480V+10%;  Frequency: ±15%

Main output

Output voltage

Maximum output voltage equals to input voltage

Output frequency

0.5 Hz to 400 Hz

Overload capacity

150% of rated output current for 60s, 200% of rated output current for 2s

Control performance

Modulation mode

3-phase PWM, 2-phase PWM

Control mode

V/f control for constant torque, V/f control for quadratic load, vector control without PG (open loop control),Energy-saving

Setting method of run command

Outer terminal, keyboard panel or serial communication

Setting method of speed command

Analog setting, keyboard, serial communication, UP/DOWN speed setting from external terminal

Speed setting resolution

Keyboard: 0.1 Hz

Analog setting: 0.05/50Hz (10bit)

Speed control precision

V/f control:±2%

vector control without PG (open loop control): ±0.2%

Speed control range

V/f control 1:40

vector control without PG (open loop control)  1:200

Acceleration and Deceleration

Time

0-3200.0s

switching frequency

1.5 kHz ~ 12 kHz, according to junction temperature automatically reduce the switching frequency

Analog input

Number

2 ways: AI1、AI2

Type

DC voltage or DC current

Maximum input range

AI1: 0 to 5VDC, 0 to 10VDC, 0/4 to 20mA DC receivable

AI2: 0 to 10VDC or PTC probe input receivable

Analog output

Number

1 way: AO1

Type

DC voltage or DC current

Maximum input range

Voltage output: 0 to 10V, Current output: 0/4 to 20mA

logic input

Number

0.75kw-11kW:LI1,LI2,LI3,LI4,AI1,AI2

15kW-500kW:LI,LI2,LI3,LI4,LI5,LI6,LI7,LI8,AI1,AI2

note:2 virtual logic input, capable of configuring AI1 and AI2 into logic input port (positive logic or negative logic)

Type

Source or Sink

Maximum input range

0-24VDC

ITEM

SPECIFICATIONS

logic output

Number

0.75kW-11kW: pulse signal output (LO-CLO)、relay output 1(T1A、T1B、T1C

15kW-500kW:pulse signal output(LO-CLO)、relay output 1、2(T1A-T1B-T1C、T2A-T2B-T2C

pulse signal output

OC,output frequencycurrentoutput、ect other function

relay output

RA-RB-RC, including a NO contact and a NC contact

Maximum switch capacity:

T1A,T1B: 3A at 250VAC, or 4A at 30VDC

T2A,T2B: 2A at 250VAC or 30VDC

Serial communication interface

RS485 interface supports Modbus protocol.

Display

4-digit LED digital display

For display of frequency setting, output frequency, fault code and parameter setting etc.

Environment

Standard

Development of VSC200 series frequency inverters follows strict international standards and relevant recommended IEC and EN standards for control devices, especially IEC/EN61800-5-1 and IEC/EN61800-3.

Altitude

Derating unnecessary when altitude is 1000m or below (Derating necessary at altitude higher than 1000m)

Ambient environment

0.75kW-11kW: Reliable operation at -10 ~ 50°C without derating. When top protective cover is taken off, the environment temperature can be as high as +50 °C. Above +50 °C, the current drops by 2.2% for each rise of 1 °C in temperature. 15kW-500kW: Reliable operation at -10 ~ 40°C without derating.

Storage: -25 ~ 70°C

Humidity

No condensed water or drip at 5 ~ 95%, In accordance with IEC60068-2-3

Impact strength

15gn for continuous 11ms, In accordance with IEC/EN60068-2-27

Maximum antipollution capacity

Class 2, in accordance with IEC/EN61800-5-1

Structure

Protection level

Top: IP41 (without removing the protective top cover). Other parts: IP20

Cooling Method

Forced Air cooling

Installation method

Wall mounted

Q: 3.7KW inverter with 2.2KW 6-pole motor running to see the inverter shows the current is more than 4A, with the amount of clamp to 2.8A
2, upstairs brothers to answer the correct, the basic frequency is the following constant speed torque control, load changes little, the current change is not large.
Q: What parts of the inverter composition
The main converter are: rectifier module, inverter module, capacitor, driver board, motherboard, shell composed of these parts!
Q: Notebook power adapter on how to look at power
Power and work voltage power adapter will be identified, you only need to distinguish between input and output on the line, the input refers to the utility power supply support, and now are generally 100V ~ 240V, so you can use in most parts of the world,
Q: What is the working principle of high voltage electrodes and frequency converters?
High-voltage inverter is the input power supply voltage above 3KV high-power inverter, the main voltage levels are 3000V, 3300V, 6000V, 6600V, 10000V and other voltage levels of high-voltage high-power inverter High voltage inverter from high - low - high; low - high; high - high points.
Q: Octopus AC Servo motor can be driven with ordinary inverter?
If it is synchronous motor, it depends on whether you choose the inverter is compatible with the synchronization machine, most of the incompatible. As you said the situation, the motor 8 pole, may be synchronous motor. Specifically, you can compare the rated speed and rated frequency to see if there is a slip rate to determine whether it is synchronous or asynchronous motor.
Q: What are the AC motor speed control methods? What are the characteristics of each
1, the frequency converter: smooth, according to the need to adjust the speed, is the future direction of the development of AC motor; (FM) 2, star, triangular connection conversion, generally in the larger motor start star start, triangular operation, Starting current. (Magnetic pole pairs) 3, there is a two-speed, three-speed motor, an increase of the winding, the main change in the stator winding connection to change the speed. (Change the number of pole pairs) The speed of change has two factors: magnetic pole logarithm, frequency
Q: Is the motor having a variable frequency motor and a variable voltage motor?
It should be no change it is the input / output current is v frequency is its input / output frequency is M / Hz
Q: Will the laptop's power adapter is not the original good?
Theoretically can be inserted into the use and will not have any obvious damage to the machine But it is best to buy the number of volt and your original consistent Original also has original benefits According to some "professional" sources claim that no original touchpad will have a slight jitter, I was not found
Q: Delta inverter reported CE4 reasons? Casually asked how many kinds of CE under a total
Is it right? The next manual to see do not understand
Q: 90KW inverter start 90KW, 4-pole motor and 6-pole motor j What is the difference? The inverter can be used for it?
Two motors can use the same frequency converter, but the motor nameplate data through the parameters to adjust the input when the inverter should pay attention to some