Technical specifications
Table 2.3: Technical Parameters of QD200 Series Frequency Inverters
ITEM | SPECIFICATIONS | |
Main Input | Rated voltage and frequency | Single-phase 200V class: 200V-240V,50Hz/60Hz |
3-phase 400V class: 380V-480V , 50Hz/60Hz | ||
Allowable value of change | Voltage: 380V-15% ~ 480V+10%; Frequency: ±15% | |
Main output | Output voltage | Maximum output voltage equals to input voltage |
Output frequency | 0.5 Hz to 400 Hz | |
Overload capacity | 150% of rated output current for 60s, 200% of rated output current for 2s | |
Control performance | Modulation mode | 3-phase PWM, 2-phase PWM |
Control mode | V/f control for constant torque, V/f control for quadratic load, vector control without PG (open loop control),Energy-saving | |
Setting method of run command | Outer terminal, keyboard panel or serial communication | |
Setting method of speed command | Analog setting, keyboard, serial communication, UP/DOWN speed setting from external terminal | |
Speed setting resolution | Keyboard: 0.1 Hz | |
Analog setting: 0.05/50Hz (10bit) | ||
Speed control precision | V/f control:±2% | |
vector control without PG (open loop control): ±0.2% | ||
Speed control range | V/f control 1:40 | |
vector control without PG (open loop control) 1:200 | ||
Acceleration and Deceleration Time | 0-3200.0s | |
switching frequency | 1.5 kHz ~ 12 kHz, according to junction temperature automatically reduce the switching frequency | |
Analog input | Number | 2 ways: AI1、AI2 |
Type | DC voltage or DC current | |
Maximum input range | AI1: 0 to 5VDC, 0 to 10VDC, 0/4 to 20mA DC receivable AI2: 0 to 10VDC or PTC probe input receivable | |
Analog output | Number | 1 way: AO1 |
Type | DC voltage or DC current | |
Maximum input range | Voltage output: 0 to 10V, Current output: 0/4 to 20mA | |
logic input | Number | 0.75kw-11kW:LI1,LI2,LI3,LI4,AI1,AI2 15kW-500kW:LI,LI2,LI3,LI4,LI5,LI6,LI7,LI8,AI1,AI2 note:2 virtual logic input, capable of configuring AI1 and AI2 into logic input port (positive logic or negative logic) |
Type | Source or Sink | |
Maximum input range | 0-24VDC |
ITEM | SPECIFICATIONS | |
logic output | Number | 0.75kW-11kW: pulse signal output (LO-CLO)、relay output 1(T1A、T1B、T1C) 15kW-500kW:pulse signal output(LO-CLO)、relay output 1、2(T1A-T1B-T1C、T2A-T2B-T2C) |
pulse signal output | ||
relay output | RA-RB-RC, including a NO contact and a NC contact Maximum switch capacity: T1A,T1B: 3A at 250VAC, or 4A at 30VDC T2A,T2B: 2A at 250VAC or 30VDC | |
Serial communication interface | RS485 interface supports Modbus protocol. | |
Display | 4-digit LED digital display | For display of frequency setting, output frequency, fault code and parameter setting etc. |
Environment | Standard | Development of VSC200 series frequency inverters follows strict international standards and relevant recommended IEC and EN standards for control devices, especially IEC/EN61800-5-1 and IEC/EN61800-3. |
Altitude | Derating unnecessary when altitude is 1000m or below (Derating necessary at altitude higher than 1000m) | |
Ambient environment | 0.75kW-11kW: Reliable operation at -10 ~ 50°C without derating. When top protective cover is taken off, the environment temperature can be as high as +50 °C. Above +50 °C, the current drops by 2.2% for each rise of 1 °C in temperature. 15kW-500kW: Reliable operation at -10 ~ 40°C without derating. Storage: -25 ~ 70°C | |
Humidity | No condensed water or drip at 5 ~ 95%, In accordance with IEC60068-2-3 | |
Impact strength | 15gn for continuous 11ms, In accordance with IEC/EN60068-2-27 | |
Maximum antipollution capacity | Class 2, in accordance with IEC/EN61800-5-1 | |
Structure | Protection level | Top: IP41 (without removing the protective top cover). Other parts: IP20 |
Cooling Method | Forced Air cooling | |
Installation method | Wall mounted |
- Q: A 4-pole AC motor into a 2-pole AC motor, the motor is controlled by the inverter, to make the maximum speed of the 2-pole motor and the original 4-pole
- If it is normal V / F control, then do not need to modify too many parameters to limit the frequency limit of 50%
- Q: What are the types of power adapter used in notebooks?
- With the increasing popularity of notebook computers, the power requirements have increased. In addition, because the battery capacity (or density) increased, charging requirements also increased - so the laptop computer power requirements have doubled. However, larger and / or hoter power adapters are not an attractive option for millions of users who carry laptops around the world. Attractive is to have a compact, but instantly charged laptop adapter. Of course, it will not produce heat, and will not cost too much. In recent years, the development of electronic products has not increased the hope in this regard, and whether the future revolution can be achieved is still a pending issue. We also want to use a laptop adapter that can be used globally without the need for a 110/220 volt operating voltage selector switch - so the laptop adapter must be designed for truly universal line voltage operation. At the same time, regulators and OEM expectations also play a role.
- Q: What is the difference between variable frequency motor and variable speed motor?
- The variable frequency motor requirements are high, are special motor, so the general motor can not use the inverter to speed. According to the above formula, it can be seen that increasing the frequency, the motor speed will be faster, reduce the frequency of the motor speed is slow, variable frequency motor core is also a special material, because the ferromagnetic material There is a saturation period, to the saturation period, regardless of whether the motor current increases, the motor will not continue to increase the intensity of the magnetic field,
- Q: I have a 11KW-4 pole inverter, now with the 4KW-4 pole motor, what impact?
- The inverter burns should be. Your motor overload is relatively large,
- Q: What are the differences and links between the soft starters and the frequency converters, and their respective principles and uses?
- The soft starter is activated by adjusting the voltage and current, and the frequency converter starts the motor by changing the frequency of the power supply. The soft starter can theoretically smooth and gradually start the motor to the maximum speed. No impact current (ordinary start-up current is 6-7 times the rated current) The inverter is best suited for tap water and fans, etc. The soft starter is not suitable for everything except for heavy load start.
- Q: Can the notebook's power adapter be mixed?
- At present, the market sales of notebook power is generally 90 watts and 65 watts two, using integrated graphics, or configure the low-end notebook, usually 65 watts. Using the independence was, the configuration of high-end, or the game audio and video of this, are generally 90 watts. If the laptop's power adapter is damaged can not be used, it is best to repair the department as soon as possible to repair. If it is for emergency, before using the two adapters to check the output power and current and voltage are conceded, as the adapter input current and voltage is not the same, should be the general household voltage is 220V, so almost all of the notebook power The adapter is 100-240V ~ 1.5A words, as long as the output current and voltage values, and wattage equal, and then one is the same interface, you can mix. In general, the voltage is stable, the output wattage is the same, the notebook is basically no harm.
- Q: How does the variable frequency motor output torque at very low frequencies?
- 1, to improve the slip of the inverter compensation coefficient 2, to improve the continuous lifting coefficient of the inverter, but the coefficient is too high there will be overcurrent. 3, with no sensor vector control can increase the motor output torque or encoder with the vector control can make the motor at low frequency to achieve the rated output torque.
- Q: There is no inverter comes with simple PLC programming function
- The PLC is programmed to handle digital and analog, the core of the entire control system. It can output the digital to the inverter, so that the inverter is reversing, you can output the analog to the inverter set speed, but also through the communication, direct control inverter
- Q: How many types of CVT are classified?
- Power transmission Power transmission is basically divided into three categories: One is the electromagnetic sliding type, it is in the asynchronous motor to install an electromagnetic slip clutch, by changing its excitation current to speed, which belongs to a more backward speed mode. Its features simple structure, low cost, easy operation and maintenance: sliding the largest, low efficiency, serious heat, not suitable for long-term load operation, it is generally only used for low-power transmission. The second class is a DC motor type, by changing the magnetic flux or change the armature voltage to achieve speed. It is characterized by large speed range, high precision, but the equipment is complex, high cost, maintenance difficulties, generally used for medium power range (dozens to hundreds of kilowatts), has been gradually replaced by AC motor. Three types of AC motor type, through the pole, voltage regulator and frequency control. The most practical application for the frequency control, that is, using a horn to obtain variable amplitude power supply, and then drive the motor speed. It is characterized by good speed performance, large range, high efficiency, can be automatically controlled, small size, wide applicable power range: mechanical characteristics in the slow speed section of constant torque, low efficiency and low efficiency is not smooth, Maintenance need professionals. In recent years, the inverter as an advanced, excellent speed device rapid development of the mechanical CVT had a certain impact.
- Q: Who knows how the inverter is calculated?
- The synchronous speed of the two-pole motor is 3000 rpm,
Send your message to us
Frequency Inverter Single-phase 200V class 400KW
- Loading Port:
- China Main Port
- Payment Terms:
- TT OR LC
- Min Order Qty:
- -
- Supply Capability:
- -
OKorder Service Pledge
OKorder Financial Service
Similar products
Hot products
Hot Searches
Related keywords