High Voltage Vertical Break Disconnector and Isolator
- Loading Port:
- Qingdao
- Payment Terms:
- TT OR LC
- Min Order Qty:
- 1 unit
- Supply Capability:
- 400 unit/month
OKorder Service Pledge
OKorder Financial Service
You Might Also Like
Specifications
1. 145KV Disconnector and Isolator
2. KEMA test report
3. ISO quality certificate
4. Good quality and after-sales service
General introduction :
GW4-40.5/72.5/126/145/170/252 Ⅲ Series, two columns, horizontally rotating type, HV, AC, disconnector
Product classifications and Main Technical Specifications :
1), Product classification
Voltage level: 40.5kV, 72.5kV, 126kV, 145kV, 170kV, 252kV.
Current level: 630A,1250A, 2000A, 2500A,3150A, 4000A.
Auxiliary earthing switch type: none earthing switch, left earthing switch, right earthing switch, double earthing switches.
2), Main Technical Specifications
Technical Specifications | Product Type | GW4-40.5Ⅲ | GW4-72.5Ⅲ | GW4-126Ⅲ |
Rated voltage kV | 40.5 | 72.5 | 126 | |
The rated current A | 1250, 2000, 3150, 4000 | |||
Disconnector | Rated peak withstand current kA | 100, 125 | ||
Rated short-time withstand current (RMS)kA | 40, 50 | |||
Rated short circuit duration s | 4, 3 | |||
Grounding switch | Rated peak withstand current kA | 100, 125 | ||
Rated short-time withstand current (RMS)kA | 40, 50 | |||
Rated short circuit duration s | 4, 3 | |||
Rated short-time power frequency withstand voltage (RMS) kV | to earth | 95 | 160 | 230 |
across open contacts | 118 | 200 | 230+70 | |
Rated lightning impulse withstand voltage (peak) kV | to earth | 185 | 350 | 550 |
across open contacts | 215 | 410 | 550+100 | |
minimum clearance in 1 min power frequency withstand voltage when ground blade closing to live part of disconnector | 53 | 94 | 164 | |
rated terminal static mechanic load N | longitudinal level | 1000 | 1000 | 1000, 1250 |
Horizontal level | 750 | 750 | 750 | |
Vertical force | 1000 | 1000 | 1000 | |
switching micro-capacitance current A | 2 | 2 | 2 | |
switching micro-inductance current A | 1 | 1 | 1 | |
switching busbar for current transfer A (busbar transfer voltage 100V) | 400V, 2500A, 100 times | |||
Radio interference level | less than 500 μV | |||
Mechanical life | 3000 | 3000 | 3000 | |
single pole weight (kg) | 120 | 200 | 260 | |
Note: All applied to an altitude of 2000m |
Technical Specifications | GW4-145Ⅲ | GW4-170Ⅲ | GW4-252Ⅲ | |
Rated voltage kV | 145 | 170 | 252 | |
The rated current A | 1250, 2000, 3150, 4000 | |||
Disconnector | Rated peak withstand current kA | 100, 125 | ||
Rated short-time withstand current (RMS)kA | 40, 50 | |||
Rated short circuit duration s | 4, 3 | |||
Grounding switch | Rated peak withstand current kA | 100, 125 | ||
Rated short-time withstand current (RMS)kA | 40, 50 | |||
Rated short circuit duration s | 4, 3 | |||
Rated short-time power frequency withstand voltage (RMS) kV | to earth | 275 | 325 | 460 |
across open contacts | 315 | 375 | 460+145 | |
Rated lightning impulse withstand voltage (peak) kV | to earth | 650 | 750 | 1050 |
across open contacts | 750 | 860 | 1050+200 | |
minimum clearance in 1 min power frequency withstand voltage when ground blade closing to live part of disconnector | 188 | 221 | 291 | |
rated terminal static mechanic load N | longitudinal level | 1000, 1250 | 1500 | 1500 |
Horizontal level | 750 | 1000 | 1000 | |
Vertical force | 1250 | 1250 | 1250 | |
switching micro-capacitance current A | 2 | 2 | 2 | |
switching micro-inductance current A | 1 | 1 | 1 | |
switching busbar for current transfer A (busbar transfer voltage 100V) | 400V, 2500A, 100 times | |||
Radio interference level | less than 500 μV | |||
Mechanical life (times) | 3000 | 3000 | 3000 | |
single pole weight (kg) | 300 | 326 | 900 | |
Note: All applied to an altitude of 2000m |
- Q: What are the distribution network equipment
- The transmission function of the power plants issued by the electricity to power consumption areas, or between adjacent grid power to send each other
- Q: AC distribution equipment including distribution box
- protection of the power supply system is between the power supply and the load are connected, disconnected, conversion
- Q: DC transmission equipment
- Power supply operation of power plant and substation in nowadays are used in DC power supply, it provides power for the control of the load and power load and DC emergency lighting load, is the foundation of modern electric power system control and protection
- Q: What is the power equipment in the distribution room?
- 10kV and below voltage rating equipment, divided into high voltage distribution room and low-voltage distribution room
- Q: Are electric wires and cables belong to distribution equipment?
- Wire rod products for the transmission of electric (magnetic) energy, information and electromagnetic energy conversion.
- Q: Distribution system equipment classification
- Electronic equipment - named meaning, is mainly composed of electronic components
- Q: An introduction to the interpretation of flexible AC transmission systems
- The parallel compensation device, such as static var compensator (SVC), thyristor controlled braking resistor (TCBR), static
- Q: Main equipment of high voltage direct current transmission
- The utility model comprises a converter, a converter transformer, a smoothing reactor, an AC filter, a DC lightning arrester and a control protection device.
- Q: What is the transmission line, what is the power distribution equipment
- Usually an overhead line, a very small number of lines (or some of them) is a cable line
- Q: Rural high voltage transmission line equipment ownership
- You do not want to what the transformer behind the high-voltage line,
Send your message to us
High Voltage Vertical Break Disconnector and Isolator
- Loading Port:
- Qingdao
- Payment Terms:
- TT OR LC
- Min Order Qty:
- 1 unit
- Supply Capability:
- 400 unit/month
OKorder Service Pledge
OKorder Financial Service
Similar products
Hot products
Hot Searches
Related keywords