Addressable Fire Alarm Control Panel
- Loading Port:
- China Main Port
- Payment Terms:
- TT or LC
- Min Order Qty:
- 1 Set set
- Supply Capability:
- 10000 Sets Per Year set/month
OKorder Service Pledge
OKorder Financial Service
You Might Also Like
Specification of Fire Monitoring Heat Alarm Detector
Network Type | Wired heat detector |
OPerating Voltage | DC 9~35V |
Standby Current | 50uA |
Alarm Indication | Red LED |
Environment | -10 °C ~ +50 °C , Humidity ≤ 95%RH |
Temp. Trip Point | 57°C (135°F) |
Alarm Output | Remote LED |
Usage of Fire Monitoring Heat Alarm Detector
Work with fire alarm system,suitable for install hospital,office,school.
Low standby current.
Anti-EMI and Anti-RFI.
Adopt SMT
Packaging & Delivery
Packaging Details : Carton Box,Gift Box
Delivery Details: 3 days
- Q: Fire alarm controller, fire alarm light, how do you need to do not light?
- Eliminate fire alarms (such as smoke detector cleaning, manual alarm button reset, etc.)
- Q: When the fan is started with a multi line control panel, what should the fan control cabinet be in (automatic, manual, stop)? Or any kind?)
- Multi line control panel is generally used for remote control. Multi line control is to control the fire facilities, is a point to point to a multi line control panel, control circuit, multi line control is controlled by the host room for manual control, some manufacturers can also participate in a multi line control linkage.
- Q: What is the difference between automatic fire alarm system, alarm controller and system linkage controller and system detector?
- Host has linkage, there is no linkage. Linkage is the fire when the automatic fire fighting equipment, such as water pumps and so on.
- Q: What does the "action master light" on the fire alarm linkage controller mean?
- The light that your host has received the feedback signal of peripheral devices (such as the valve open or flow action) for this feedback signal, are unable to clear the host complex, because the peripheral device is not reset.
- Q: SIEMENS fire alarm controller alarm communication fault? What is the reason?!
- If there is a network system, check the network board, networking lines and the host connected to the network is normal, and check whether the network settings are correct.
- Q: What is the difference between the return line of the fire control module and the normal opening of the controlled device?
- Often open, also known as: dynamic combination; often closed, also known as: dynamic broken, is for buttons, electromagnetic relays, electromagnetic contactor and other electronic devices.Normally open, understood as "usually disconnected," or "broken under normal conditions"";Normally closed is understood as "usually closed," or "normally closed."";
- Q: How much is the voltage of the fire controller?
- Automatic fire alarm and fire control system is one of the systems that Intelligent Building has to set up. It can automatically monitor the smoke, fire or heat generated by the fire when the fire detector is arranged on the spot. When a fire occurs, a sound light alarm signal is sent out, and the relevant fire fighting equipment is linked together to realize the detection and alarm and control the fire extinguishing.
- Q: Should the weak electricity and fire control room be made of anti-static floor during construction? Will it affect the acceptance later?
- Is the computer room and the fire control room must be laid in accordance with the norms of anti-static flooring, this is in accordance with the specification must be acceptance of the floor after installation, according to the design requirements along the room installation skirting board (wood, stone can be). The baseboard should be firm, flat and horizontal, and the error shall not exceed 3mm within the range of 5m.
- Q: The fire control cabinet shows the main electrical fault. What's the matter?
- Usually because of fire fighting equipment need to double circuit power supply, to ensure that there is power in case of fire, so the fire control cabinet and main electric power, the main power off after main power failure, and will immediately switch to the standby power (power is usually battery, or second way power).When the main power failure is shown, it is important to grasp the cause, check the equipment and restore the power supply.
- Q: Is the fire alarm and linkage controller the main fire engine?
- For example, the controller is equivalent to the human hand, feet, is used for practical work; and fire engines are similar to the human brain, is used to judge and send instructions.
1. Manufacturer Overview
Location | Quanzhou, China |
Year Established | 1988 |
Annual Output Value | Above US$ 0.8 Million |
Main Markets | Mid East, Africa, Europe |
Company Certifications |
2. Manufacturer Certificates
a) Certification Name | |
Range | |
Reference | |
Validity Period |
3. Manufacturer Capability
a) Trade Capacity | |
Nearest Port | Shanghai, Shengzhen |
Export Percentage | 40% |
No.of Employees in Trade Department | 210 People |
Language Spoken: | English;Chinese;Spain ;Alabic |
b) Factory Information | |
Factory Size: | Above 7,000 square meters |
No. of Production Lines | Above 6 |
Contract Manufacturing | OEM Service Offered;Design Service Offered |
Product Price Range | Average |
Send your message to us
Addressable Fire Alarm Control Panel
- Loading Port:
- China Main Port
- Payment Terms:
- TT or LC
- Min Order Qty:
- 1 Set set
- Supply Capability:
- 10000 Sets Per Year set/month
OKorder Service Pledge
OKorder Financial Service
Similar products
Hot Searches
Related keywords