Who knows how big transformers and lines the 36V transformer uses in lighting?
The sectional area of the wire can be calculated according to the electric power formula. The current required by the wire is calculated, and then the reference to the national standard "500 volt copper core insulated wire, long term continuous load allowable ampacity meter" is selected.
The transformer zero line has broken, has the result to the household illumination circuit?
The zero line is connected to the transformer neutral point of transformer, three FireWire for its voltage is 220 volts, according to regulations, the total can not take the zero line fuse, switch, because once the zero line is disconnected, the rest of the line will no longer be a neutral line, into the use of electrical appliances connected to two the conductor, according to the characteristics of series circuit, each phase with electrical voltage, on load distribution, change the original load smaller which phase by using electrical appliances, will damage due to excessive voltage.
Is the substation separate from the power and illumination transformer?
The power and illumination of the substation are all used on a transformer, which is separated by power and lighting by the station screen of this transformer.
What type of low voltage transformer should be adopted for safety lighting power supply?
Isolated transformer, once 380V or 220V, two voltage, 36V, 24V, 12V, several categories, do not allow the use of autotransformer.
How many A leakage protection switches are used in 5000VA lighting transformers?
Secondary current =5000VA/220=22A, you can select the 32A leakage protection switch.
How many power illuminator can 5Kva 36V transformer drive?
The load capacity of the transformer is 70% of its nominal power, so it is concluded that the transformer you provide can drive the 3.5KVA 36V lighting appliance (which is used in normal condition and environment)
Line lights, lighting transformers in use!! Can live line work?!! Be afraid of electric shock 40
What you think? Your light is 220V, right. Over 36V, it's better not to live with electricity unless there is good protection
Why can't autotransformer be used as transformer for safety lighting?
The main and auxiliary coils of the autotransformer have common parts. Once the short-circuit is made, the lighting circuit is directly connected with the high voltage circuit, which is very dangerous